Welcome to our site! EDAboard.com is an international Electronics Discussion Forum focused on EDA software, circuits, schematics, books, theory, papers, asic, pld, 8051, DSP, Network, RF, Analog Design, PCB, Service Manuals... and a whole lot more! To participate you need to register. Registration is free. Click here to register now.

Problem with unbalance detection in three phase system

Status
Not open for further replies.

electronicsIUST

Member level 3
Joined
Feb 12, 2017
Messages
67
Helped
0
Reputation
0
Reaction score
0
Trophy points
6
Activity points
575
Hello! I want to check voltage unbalance in a three phase system. I have used the below circuit for checking unbalance. But in normal operation that all three phase are approximately equal there is'nt zero voltage difference between points N and N'. I have near 5 Vrms in normal operation, while in some weeks ago there was near 0 voltage difference. Do anyone know what is the problem??

**broken link removed**
 

Do you mean the problem is with power grid that supplies 3 phase?! When I measure phase voltages there is little difference between them! and 3 resistors also are equal.
 

There are two distinct unbalance conditions: The three phases have unequal peak voltages AND/OR the phase relations between the phases are not equal.

In general, we expect the load too be symmetric on the three phases. This condition is often not fulfilled. The effect depends on the source impedance.

Your load is not the only load on the system; other large loads on the same circuit can affect the phase and amplitude. If the line voltages are 220/440V, then 5V on the neutral due to unbalanced current is rather small and nothing to worry.

If the voltage gets over 10% of the line voltage, you need to redistribute the other loads so that some symmetry is attained.
 