Sizing transformers for AC voltage stabilizers employing series topology

Rating: 2 votes, 4.50 average.
This article is intended to be a quick guide on calculation of transformers used in AC voltage stabilizers which employes series topology. Such model is rarely used in low power equipments due to the relatively more complex control system required for drive the switching devices, but is specially suitable for employing at high power equipments, on what the weight of a conventional transformer (multi-taped) would be prohibitive, besides the fact that it reaches better resolution in the output compared to the standard approach.

A case study will be a stabilizer designed to handle an input ranging on ± 15% with a resolution of 1%.
An illustration of the circuit is shown below, where we initially note the presence of 4 transformers:

Click image for larger version. 

Name:	Topologia.PNG 
Views:	2370 
Size:	14.0 KB 
ID:	106544

Basically, it performs a sum or subtraction of voltage by a binary logic, as follows:

Click image for larger version. 

Name:	image002.jpg 
Views:	489 
Size:	22.2 KB 
ID:	106545

The table bellow show the logic required for the 4 switches work integrated:

Click image for larger version. 

Name:	image004.png 
Views:	507 
Size:	81.5 KB 
ID:	106546

An interesting aspect of this concept is the fact that instead of working with a single transformer leading 100% of the power, we now have 4 smaller transformers, each one manipulating respectively 8%, 4%, 2% and 1% of the total power, which means that the total weight of the equipment will be substantially reduced. This weight reduction can be estimated by the following analysis:

The voltage on each transformer VTR is proportional to its turns ratio, and if we express the equation as a function of percentage, we obtain:

Click image for larger version. 

Name:	image006.jpg 
Views:	337 
Size:	2.6 KB 
ID:	106547 ( 1 )

Knowing that the current flowing in the output is the same at transformers, we can apply the formula P = VI, as follows:

Click image for larger version. 

Name:	image008.jpg 
Views:	344 
Size:	2.6 KB 
ID:	106548 ( 2 )

In order to obtain a relationship between dimensions and power of transformer ( in the case, of iron-silicon ) we can apply the well known equation which defines the cross-sectional area of the core as function of the power driven by its magnetic flux, as follows:

Click image for larger version. 

Name:	image013.png 
Views:	352 
Size:	1.5 KB 
ID:	106674 ( 3 )

Since the focus here is only to present a comparison with the original topology, the constant value above does not matter, because will be eliminated on equation below, which provides the ratio of the cross sections of two topologies:

Click image for larger version. 

Name:	image009.png 
Views:	330 
Size:	3.7 KB 
ID:	106550 ( 4 )

We can replace the variable PTR of the equation ( 4 ) by the value equation ( 2 ), obtaining the result:

Click image for larger version. 

Name:	image012.png 
Views:	374 
Size:	3.4 KB 
ID:	106551 ( 5 )

For the sake of clarity, in the following steps, we will refer to this relation by constant below:

Click image for larger version. 

Name:	image014.png 
Views:	334 
Size:	2.4 KB 
ID:	106552 ( 6 )

The result will be calculated for each transformer, yielding the following:

Click image for larger version. 

Name:	image015.png 
Views:	359 
Size:	7.7 KB 
ID:	106553 ( 7 )

However, the section of the transformer itself does not bring us too much information about its weight.
We know that there is a relationship between the area and volume of 2 objects linearly proportionals:

Click image for larger version. 

Name:	image016.png 
Views:	340 
Size:	2.1 KB 
ID:	106668 ( 8 )

Just as before, for clarity purpose, we can identify the volume ratio by the following constant:

Click image for larger version. 

Name:	image017.png 
Views:	329 
Size:	2.7 KB 
ID:	106669 ( 9 )

Applying constants ( 6 ) and ( 9 ) inside equation ( 8 ), yields:

Click image for larger version. 

Name:	image018.png 
Views:	328 
Size:	3.0 KB 
ID:	106670 ( 10 )

Calculating the values of equations ( 7 ) and ( 9 ) above results in the table below:

Click image for larger version. 

Name:	image019.png 
Views:	365 
Size:	8.3 KB 
ID:	106675

Note that the sum of the last column generates the following result:

Click image for larger version. 

Name:	image020.png 
Views:	332 
Size:	2.4 KB 
ID:	106672 ( 11 )

Conclusion :
For the above case study, the total weight for the four transformers employing serial topology is ~ 1/3 than would be required in standard topology, based on multi-tap.
Tags: None Add / Edit Tags