Welcome to our site! EDAboard.com is an international Electronics Discussion Forum focused on EDA software, circuits, schematics, books, theory, papers, asic, pld, 8051, DSP, Network, RF, Analog Design, PCB, Service Manuals... and a whole lot more! To participate you need to register. Registration is free. Click here to register now.

Recent content by SvenH

  1. S

    [SOLVED] APC Back-UPS CS 650 BK650EI dead - "On Battery" on, low voltage on battery

    Re: APC Back-UPS CS 650 BK650EI dead - "On Battery" on, low voltage on battery Problem was solved with a replacement battery. UPS works fine now. I did not try to replace any capacitors.
  2. S

    [SOLVED] APC Back-UPS CS 650 BK650EI dead - "On Battery" on, low voltage on battery

    Re: APC Back-UPS CS 650 BK650EI dead - "On Battery" on, low voltage on battery Thanks for your helpful replies. I tested a bit more and indeed the unit seems to drain the battery at startup, but the voltage of the broken battery is too low. I have ordered a replacement which I expect to arrive...
  3. S

    [SOLVED] APC Back-UPS CS 650 BK650EI dead - "On Battery" on, low voltage on battery

    Anyone know where to start with this one? After years of dis-use, I fired up my APC Back-UPS CS 650 BK650EI to no avail. The "On Battery" light stays on and the unit does not respond or supply power. This happens with or without battery. It only supplies 5.86V to the battery terminals so I...