Welcome to our site! EDAboard.com is an international Electronics Discussion Forum focused on EDA software, circuits, schematics, books, theory, papers, asic, pld, 8051, DSP, Network, RF, Analog Design, PCB, Service Manuals... and a whole lot more! To participate you need to register. Registration is free. Click here to register now.

Recent content by avino

  1. A

    EDP70 or Chloride EPEM 20KVA fault problem

    Hi Guys! anyone can help me on my 20KVA Chloride there is an alarm that i cant rectify.. the problem is Static Switch Locked on Inverter i already try to switch on/off the Q1 and Q2 but the fault still exist static switch and reserve supply indicator is flashing but there is no buzzer. beside...
  2. A

    Chloride EDP-50 UPS Service Manual

    as i know reserve supply and main input rectifier is the same as well as the maintenance by-pass. just a wild guess with a bit of confidence i think you should connect the wire of reserve supply from mains input then connect it to transfer switch of the ups if you can locate the board.
  3. A

    Chloride 20KVA EPEM - help with UPS needed

    yup! its already rectified the problem i try to send e-mail to chloride team and they told as about this Static switch setting of sw2.1 = on sw2.2 = off for 230Vac sw2.1 = off sw2.2 = off for 220vac now there's no more alarm on the unit. anyway ups has an input isolation transformer 380/208vac...
  4. A

    Help me extend the autonomy of an UPS

    UPS question! In normal circumstances battery inside a UPS unit is charged with limited current till it is "full" and then the charging mode is switched from "charge" to "trickle". Connecting directly external 80Ah battery will most likely not damage the UPS and you have good chances that this...
  5. A

    Chloride 20KVA EPEM - help with UPS needed

    Chloride 20KVA EPEM Can anyone help me about the problem on UPS reserve supply fault (reserve supply low) this UPS alarm always but when i try to check the input its 367-370 on mains input although its transitory (its iether back to normal or permanently fault) no action required on the side of...
  6. A

    Request for chloride and Victron UPS manuals

    I have a Manual for Chloride 90net but if you want i can send you one copy of it, anyway im working also as UPS tech i handle the liebert/emerson and chloride epem and 90-net so if you have any question regarding this two ups i can help you but in return you have to help me also, exchanging...