| Author |
Message |
mayur_dand
Joined: 24 Jun 2003 Posts: 25 Location: ankleshwar
|
11 Oct 2003 17:38 pc/ppi cable |
|
|
|
|
hello friends
couple of days back i burnet my pcppi cable and mpi on also now can any on suggest me hoe to communicate with plc using the cheap alternative ok
it's urgent for me
if u can help me please mail or pm me at mayur_dand(at)rediffmail.com
|
|
| Back to top |
|
 |
jackrs
Joined: 18 Apr 2003 Posts: 68 Location: Dark side of the moon.
|
12 Oct 2003 11:59 make a pc/ppi cable |
|
|
|
|
Hi
Try this circuit.
It works only with s7 200.
Best Regards
jackrs
|
|
| Back to top |
|
 |
ferrungas
Joined: 11 Sep 2002 Posts: 2
|
14 Oct 2003 23:27 pc/ppi cable singapore |
|
|
|
|
| how can i connect to S5? could you help me?
|
|
| Back to top |
|
 |
jackrs
Joined: 18 Apr 2003 Posts: 68 Location: Dark side of the moon.
|
15 Oct 2003 11:48 pc/ppi cable picture |
|
|
|
|
Hi ferrungas
When i downloaded the file "ppi cable for s7_200", i remenber that autor said in you web page "it work only whit s7_200" !!!
But you can try this other circuit.
I never had tested any of this circuits.
Try at your own risk !!!
Best Regards
jackrs
|
|
| Back to top |
|
 |
7rots51
Joined: 17 May 2002 Posts: 1427 Helped: 14
|
23 Jul 2004 14:20 s7 200 wiring diagram cable |
|
|
|
|
| Is it work for s7-300?
|
|
| Back to top |
|
 |
kimkhan
Joined: 15 Aug 2004 Posts: 2
|
15 Aug 2004 21:50 s7200 programmer usb cable schematic |
|
|
|
|
Can you guys post me the diagram and an alternative software to use to program /upload/Download S7 -300 PLCs.
Thanks,
Kim
|
|
| Back to top |
|
 |
Milan-Sr
Joined: 02 Oct 2004 Posts: 8 Location: Serbia
|
23 Jan 2005 14:18 s72xx_ppi_197.rar |
|
|
|
|
Hi,
I made PC/PPI cable using your schematic,but Step 7 Microwin show me the error.
I have 2 questions:
1. Can you give me value of resistor on schematic (R1)?
2. Do I have to connect RST pin oc PC side somewere?
Thanks
Milan
|
|
| Back to top |
|
 |
jackrs
Joined: 18 Apr 2003 Posts: 68 Location: Dark side of the moon.
|
23 Jan 2005 15:40 ppi cable schamatic |
|
|
|
|
Hi Milan-Sr
As you can see in the file "s72XX_ppi_197.rar", in the file "NOTE.TXT", R1=1200Ω.
To all connections please refer to file "Pc_s7_1_200 adapter" in the file "s72XX_ppi_197.rar".
Note: i never build this circuit...
Regards.
jackrs
|
|
| Back to top |
|
 |
Milan-Sr
Joined: 02 Oct 2004 Posts: 8 Location: Serbia
|
23 Jan 2005 19:32 plc 222 dcdcdc |
|
|
|
|
Hi,Jackrs
Error:
Master exist on the profibus network and the cuuuent device does not support master.
????
What now??
Regards.
Milan
|
|
| Back to top |
|
 |
tuanha
Joined: 01 Feb 2005 Posts: 2
|
01 Feb 2005 11:05 s7-200 circuit |
|
|
|
|
Please post again some schematic/diagram of a "cheap" ppi-cable?
Thanh you very much.
|
|
| Back to top |
|
 |
Google AdSense

|
01 Feb 2005 11:05 Ads |
|
|
|
|
|
|
| Back to top |
|
 |
inglaof
Joined: 06 Jan 2006 Posts: 7 Helped: 1
|
22 Mar 2006 7:21 pc connect to s7 200 schematic |
|
|
|
|
Hi Milan Sir...
Well, the schematic of the cable shown bellow on the links should work at least perfectly. In the link, there is also a doc file in which the autor explain that he used succesfuly, at least with the same link troubles with the original one, maybe your troubleshoot must be the configuration of the link, maybe the PC acts like master and the device is configured as master too, im not shure, i'll hope soon try this cable with an S7-200 that i eraned in a exchange for a Logo jejeje
And, the circuit diagram of the link about the cable, its not a big secret from Siemens, the circuit only transform RS232 voltage levels and logic to TTL logic, and after traslate the logic from TTL to RS485 signals, so, thats the big deal, only transform that signals, and in that case, the energy or voltage source from the circuits comes from the PLC and not from the PC port, so, if you already build that cable, and have troubles, check the ground's, you must bypass or join both grounds to read and transmit correct information trougtht both BUS...
See ya fellows, its a nice place this forum, every time i visit it, im more surprised..
Greetings from Mexico... forgive my rude english, i barely speak it... see ya..
|
|
| Back to top |
|
 |
microcozmoz
Joined: 12 Jul 2003 Posts: 20 Helped: 1
|
18 Apr 2006 8:41 ic 75176 circuit diagram |
|
|
|
|
Dear Friends,
Are u sure about this circuit is working?
Please let me know cause I made the circuit but cant connect to PLC..
|
|
| Back to top |
|
 |
macir
Joined: 18 Apr 2006 Posts: 9
|
20 Apr 2006 19:25 pc to ppi cable circuit diagram |
|
|
|
|
Hii
I tried again this circuit and I made it. it is working. It was succesfull
thanks
|
|
| Back to top |
|
 |
zanor
Joined: 17 Feb 2006 Posts: 77 Location: Norway
|
23 Apr 2006 20:46 pc ppi cable |
|
|
|
|
Hi!
I just made the pc/ppi cable from the schematics above and I just get the "Masers exist on the PROFIBUS ....... " error too.
macir: What did you do to get around this problem?
|
|
| Back to top |
|
 |
macir
Joined: 18 Apr 2006 Posts: 9
|
24 Apr 2006 16:22 siemens s7 200 to a pc |
|
|
|
|
Hi! zanor
ther are two problem picture three.
1- max 232 power pin (16 food) no (+) power you mut give (+) power this point
2- 75176 power pin is empty you must give (+) power this point.
excuse me my english not good
if you want I can send email picture 3
I have got s7 200 22cpu and it is working good this cable
see you next
Love from Turkey
|
|
| Back to top |
|
 |
zanor
Joined: 17 Feb 2006 Posts: 77 Location: Norway
|
24 Apr 2006 21:27 232 schematic 75176 |
|
|
|
|
| macir wrote: |
Hi! zanor
ther are two problem picture three.
1- max 232 power pin (16 food) no (+) power you mut give (+) power this point
2- 75176 power pin is empty you must give (+) power this point.
excuse me my english not good
if you want I can send email picture 3
I have got s7 200 22cpu and it is working good this cable
see you next
Love from Turkey |
Thank you for replying!
My + pins are OK.
But should the RX LED always be on? it goes off if I remove the 75176 from it's socket. And also the error msg goes away if I remove the 75176 IC, but then of course I get a timeout when trying to communicate with my PLC
I found that my 75176 IC may be broken, because when it's not connected to the PCB I get 15 OHm between pin 5 and 6.
This can't be normal or is it? Could you please measure your's?
BTW, I also have the S7 200 222CPU.
|
|
| Back to top |
|
 |
macir
Joined: 18 Apr 2006 Posts: 9
|
27 Apr 2006 21:16 s7-200 pc connection |
|
|
|
|
Hi! zanor
I first made this circuit Rx and Tx led always on
and there were comunication fals after I made again connect 232 16.pin (+) and 75176 8. pin (+)
Tx and Rx led only on as fliflop when knowledge flov (232 IC 15.pin gnd and 75176 5.pin gnd Pc connector 5.pin gnd) all of them must be
my email
macir26(at)hotmail.com
please send me email adress
I will send you my change on board
I have got s7 200 222 (DCDCDC and DCDCRLY)cpu and it is working good this cable
see you
Added after 20 minutes:
Hii
Ic pins
max 232
1 o U o 16 (+)
2 o o 15 gnd
3 o o 14
. .
. .
. .
75176
1 o U o 8 (+)
2 o o 7
3 o o 6
4 o o 5 gnd
|
|
| Back to top |
|
 |
zanor
Joined: 17 Feb 2006 Posts: 77 Location: Norway
|
05 May 2006 5:55 75176 circuit diagram |
|
|
|
|
Got it working now.
My SN75176 was broken. Works like a charm now
|
|
| Back to top |
|
 |
macir
Joined: 18 Apr 2006 Posts: 9
|
27 Apr 2007 20:51 pc cable s7-200 circut |
|
|
|
|
Hii
if you want to learn this circuit
you can send mail macir26(at)hotmail.com
I can send circuit shematic
|
|
| Back to top |
|
 |
molehiya
Joined: 02 Oct 2007 Posts: 2
|
10 Oct 2007 11:15 s7-200 cable |
|
|
|
|
The circuit is working.
My problem is about the boudrate of the communication between plc and pc.
The given circuit is communicate 9600kbps. Is there a any way to increase the
boudrate upto 115200 kbps? Anybody know it?
|
|
| Back to top |
|
 |
macir
Joined: 18 Apr 2006 Posts: 9
|
17 Dec 2007 21:10 how built cable s7-200 |
|
|
|
|
hii Molehiya
I think you must change your connecting point setting
if you can t change this I will send email "how to change "
|
|
| Back to top |
|
 |
macir
Joined: 18 Apr 2006 Posts: 9
|
30 Dec 2008 20:54 s7 200 cable |
|
|
|
|
hii
I can help if you mail to me
I sent circuit a lot of friends
many friends it worked
best regards
|
|
| Back to top |
|
 |
macir
Joined: 18 Apr 2006 Posts: 9
|
05 May 2009 20:12 pc/ppi cable 11bit setting |
|
|
|
|
I improved this cable
I can help if you mail to me
I can send circuit shematic and PCB
best regards
|
|
| Back to top |
|
 |
venix
Joined: 20 Mar 2008 Posts: 86 Helped: 9
|
|
| Back to top |
|
 |
macir
Joined: 18 Apr 2006 Posts: 9
|
07 May 2009 20:50 diagram for s7-200 pc ppi cable |
|
|
|
|
Thanks
A good link
Best regards!
|
|
| Back to top |
|
 |
vietplc
Joined: 18 Jan 2009 Posts: 2
|
10 May 2009 12:39 problems communicating with s7 222 cpu |
|
|
|
|
@macir:
I received your file but I do not know the software to open file with extention LYT.
PLS show me the name of software to open file
Thanks so much!
|
|
| Back to top |
|
 |
macir
Joined: 18 Apr 2006 Posts: 9
|
10 May 2009 20:43 pc/ppi cable trouble |
|
|
|
|
You must use " proteus (ARES)" program for this circuit
Best regards!
|
|
| Back to top |
|
 |
vietplc
Joined: 18 Jan 2009 Posts: 2
|
24 May 2009 12:54 s7-200 to pc |
|
|
|
|
| macir wrote: |
You must use " proteus (ARES)" program for this circuit
Best regards! |
Thanks so much
I have drawn a new pcb in Eagle and used 2 port 9 pins
|
|
| Back to top |
|
 |
Medtronic
Joined: 19 May 2005 Posts: 165 Helped: 11 Location: Egypt
|
12 Oct 2009 11:34 Re: most cheap way of communicating the s7-200 with the pc |
|
|
|
|
Dear jackrs
Please advice me how to test your cable with s7-200 and pc ,give an example with pc software and s7-200 program
Best Regards
MedTronic
|
|
| Back to top |
|
 |
Medtronic
Joined: 19 May 2005 Posts: 165 Helped: 11 Location: Egypt
|
21 Oct 2009 20:35 Re: most cheap way of communicating the s7-200 with the pc |
|
|
|
|
| Why there is no answer
|
|
| Back to top |
|
 |