Post03 Jan 2009 7:09   

scada


I am incharge of the project to replace telemechanique PLC system with that Siemenn S400 system. The problem i face is the link to the SCADA software. Previous telemechanique system is linked to the SCADA Ssoftware using MODBUS (i guess). The Siemens system is using TCP/IP. I don't know how to link this Siemens system which is using TCP/IP to the SCADA system using MODBUS.
What arrange i can make?. Is it possible?
Please help
Thanks a lot in advance
Back to top
khongai



Joined: 20 May 2005
Posts: 245
Helped: 5


Post05 Jan 2009 9:00   

tentang scada


In PLC S400, you can use some MODBUS module to connect to SCADA software, But now all the SCADA software support alot of protocol (Modbus, Profibus, and also TCP/IP).
Back to top
rmmaran



Joined: 22 Jun 2006
Posts: 28


Post05 Jan 2009 10:18   

free scada to read modbus registers


Thanks. But I need some detailed steps to connect a MODBUS running SCADA to Siemens PLC. Is there any configurations that we must do? or just connect? pls help
Back to top
marie65



Joined: 15 Jan 2002
Posts: 217
Helped: 10


Post30 Jan 2009 22:09   

saya plc software


A SCADA system is connected to the PLC using "tags" that are basically memory location found in the PLC and are cyclic read/write. The MODBUS or TCP/IP are only protocols to do this read/write access. The interfaces could be serial (rs485, RS232), ethernet, wireless etc. This memory location contains varibles that could be digital input/output, analog variables, flags, alarms, strings, recipes etc. The main problem is not what interface/protocol you use (rs485/rs 232/modbus tcp/ip or modbus/profibus/tcp/ip). The problem is that the PLC software have to match the existing tags already declared on the SCADA software. That means that you need to know the address location of the tags in the SCADA runtime and you have to design the PLC software using the same address. Not very likely to happen.
The solution is to rebuild the SCADA runtime based on the new tags that you declared on the Siemens PLC. But this suppose that you have the sources and design software for your existing SCADA.
Back to top
avra



Joined: 22 Oct 2001
Posts: 28
Location: Serbia


Post31 Jan 2009 0:29   

modbus+plc


You need to have S7 400 driver in your SCADA, choose it instead of MODBUS driver, and remap old MODBUS like adresses with new S7 ones for all your tags. Some SCADA vendors provide free drivers, some charge them. If direct communication driver for S7 400 doesn't exist in your SCADA, then you can use OPC client driver (which every SCADA has) and install SIMATIC NET with proper licence for S7400 ethernet (SIMATIC NET is an OPC server for all S7 series).
Back to top
trekkytekky



Joined: 04 Apr 2009
Posts: 77
Helped: 6
Location: Perth


Post08 Jul 2009 16:31   

how to connect a scada system to a plc


Marie65 and Avra have hit the nail on the head.

The easiest is to export your tag database from your scada, modify in say excel to match your Seimens tags and re import, replacing existing tags with updated. Then redefine your IO Device driver from Telemech to Seimens. Then recompile and restart.

Be aware that some scada's have an issue if their database is in a different format as excel sometimes adds unwanted information. For example Citect has an excel addin to make sure that M$ doesn't stuff up the tag database.

I've used this method to remap over 3000 tags when I replaced an old modbus PLC with a new ModbusTCP/IP PLC.
Back to top
Google
AdSense
Google Adsense




Post08 Jul 2009 16:31   

Ads




Back to top
rizky_aewis



Joined: 15 Jul 2009
Posts: 1
Location: indonesia


Post15 Jul 2009 5:53   

tugas akhir scada


saya sedang mengerjakan tentang tugas akhir yang temanya tentang scada?
tapi masih bingung harus mulai dari mana,software yang dipakai yang mana?
tolong dong kasih tahu mana software yang sekiranya mudah dan sekaligus tutorialnya,makasih?
Back to top
Arabic versionBulgarian versionCatalan versionCzech versionDanish versionGerman versionGreek versionEnglish versionSpanish versionFinnish versionFrench versionHindi versionCroatian versionIndonesian versionItalian versionHebrew versionJapanese versionKorean versionLithuanian versionLatvian versionDutch versionNorwegian versionPolish versionPortuguese versionRomanian versionRussian versionSlovak versionSlovenian versionSerbian versionSwedish versionTagalog versionUkrainian versionVietnamese versionChinese version
Post new topic  Reply to topic    EDAboard.com Forum Index -> Industrial, Robotics and Automatics Forum -> SCADA system
Page 1 of 1 All times are GMT + 1 Hour
Similar topics:
scada system (3)
DCS and SCADA system (2)
requst information about scada system (3)
SCADA (1)
SCADA beginner (14)
Scada WinCC (1)
Scada tool ? (4)
scada beginner (13)
Scada for Delphi (2)
Scada and siemens (9)


Abuse || Administrator || Moderators || Support us || sitemap
topic RSS