S7-400(Communication failure with IM151)


Post new topic  Reply to topic    EDAboard.com Forum Index -> Robotics and Automatics Forum -> S7-400(Communication failure with IM151)
Author Message
zare.v



Joined: 11 Mar 2008
Posts: 4


Post13 Mar 2008 8:11   

plc s7 400 communication


I have recently faced a problem for our PLC(S7-400) which controls our Electro-compressor.(you can find our configuration in this address:http://www.edaboard.com/viewtopic.php?p=996387#996387)
Our PLC has communication wit site via two paths, one is via "Fiberoptics Module Profibus"(OZD Profi 12M) and the other is via ET200 S(IM151: 6ES7 151 -1AA02-0ab0). The problem is the IM151 communication failure with PLC, On IM 151 the "SF" led is lit and the "BF" led is blinking, on CPU the "BUS2" is also blinking.
I reloaded the configuration file into PLC, replaced the IM151 with a healthy one, even changed the interconnection cable but the problem was not fixed.
I would greatly appreciate if someone can advise me on resolving the matter.
Back to top
Google
AdSense
Google Adsense




Post13 Mar 2008 8:11   

Ads




Back to top
murali_dece



Joined: 21 Jul 2004
Posts: 9
Location: india


Post18 Mar 2008 16:46   

im151 blinking


we are using the same plc s7 400,in our cement plant.bus fault occurs due to bad end termination of profibus cable.profibus cable is parallel to all IM 151 modules but profibus cable at IM151 module end should be terminated (i.e physically last IM module in profibus network). end termination is done by puting the dip swith "on" which is provided on profibus connector, remaining all profibus conectors dip switches are in "off" position other wise bus fault will blink.

system fault will occur when all modules which are assigned in plc project are not recognised by the plc. both problems are related,
Back to top
Arabic versionBulgarian versionCatalan versionCzech versionDanish versionGerman versionGreek versionEnglish versionSpanish versionFinnish versionFrench versionHindi versionCroatian versionIndonesian versionItalian versionHebrew versionJapanese versionKorean versionLithuanian versionLatvian versionDutch versionNorwegian versionPolish versionPortuguese versionRomanian versionRussian versionSlovak versionSlovenian versionSerbian versionSwedish versionTagalog versionUkrainian versionVietnamese versionChinese version
Post new topic  Reply to topic    EDAboard.com Forum Index -> Robotics and Automatics Forum -> S7-400(Communication failure with IM151)
Page 1 of 1 All times are GMT + 1 Hour
Similar topics:
BJT ESD failure, anyone has experience with that? (10)
powerline communication with max2986 compatible with 220V? (1)
Caller ID with MT8843 - communication with atmega8 (2)
300-400 antenna (7)
IBM MAINFRAME AS 400 (1)
Oscillator 400~600 MHz (2)
400 VDC from 230V AC (10)
RF3809 2W 400-2500MHZ AMP (2)
Radio Shack Realistic DX-400 Receiver (4)
Sending data over 300-400 m? (4)


Abuse || Administrator || Moderators || Support us || sitemap
topic RSS