| Author |
Message |
7rots51
Joined: 17 May 2002 Posts: 1427 Helped: 14
|
19 Jul 2005 17:52 loadcell connection |
|
|
|
|
Hello
How I can connect loadcell to s7-200 plcs(siemens)? Loadcell needs high precision ADC(more than 12 bits).
|
|
| Back to top |
|
 |
khongai
Joined: 20 May 2005 Posts: 245 Helped: 5
|
20 Jul 2005 11:45 s7-200 connection |
|
|
|
|
you must use indicator weight and then depend on indicator weight you must select interface modul for PLC ( such as analog, BCD, RS232, ...).
Goods lucks.
|
|
| Back to top |
|
 |
7rots51
Joined: 17 May 2002 Posts: 1427 Helped: 14
|
20 Jul 2005 12:41 plc for load cell |
|
|
|
|
| can I connect siwarex load cell modules to s7-200 PLC?how?
|
|
| Back to top |
|
 |
sklux
Joined: 30 Jan 2002 Posts: 58
|
20 Jul 2005 17:16 plc s7 module connection |
|
|
|
|
Connecting load cells must be done with the right material :
a load cell is basically an high precision resistor.
So a Δ wheight gives a Δ resistor. You can measure this with a millivoltmeter.
Of course the wiring of your loadcell to your plc as a direct influence on your
measure.
If you really want o use a S7-200 try to find a module that convert the measure of the
wheight to a 4-20 mA signal which is easier to handle with a PLC.
Try Metler Toledo they are specialists on the wheighing field you ll maybe find such
module
|
|
| Back to top |
|
 |
Google AdSense

|
20 Jul 2005 17:16 Ads |
|
|
|
|
|
|
| Back to top |
|
 |
7rots51
Joined: 17 May 2002 Posts: 1427 Helped: 14
|
21 Jul 2005 11:58 siwarex ma |
|
|
|
|
Hi sklux:
I know that there are some loadcell modules that convert weight to 4-20mA,
But the ADC modules of s7-200 have 12 bit resolution ,and in real world only 8 bits of them are useful.so I can not use s7-200 ADC(AI) modules!
This is a very weak point for siemens that not suport high presicion bridge sensors!
|
|
| Back to top |
|
 |
sklux
Joined: 30 Jan 2002 Posts: 58
|
25 Jul 2005 1:02 connecting s7 200 |
|
|
|
|
In fact S7-200 is low range PLC of Siemens. You could find certainly more accuracy
on S7-300/400. So is Profibus a standard on the industry, you may find an interface
that can handle the connection with the load cell and give the result as a profibus slave.
|
|
| Back to top |
|
 |
7rots51
Joined: 17 May 2002 Posts: 1427 Helped: 14
|
27 Jul 2005 14:21 siwarex load cell s7 200 |
|
|
|
|
I got this link from siemens support,use siwarex modules:
"It is possible to use the Siwarex U with S7 200.
Please look in the internet under the following address:
http://support.automation.siemens.com/WW/view/en/1853353
Additional I am informing you that Siemens works on a new module
especially for S7 200.This new module will come to market in the next year.
If you have further questions don't hesitate to contact me again."
|
|
| Back to top |
|
 |